- Description
- Ratings & Certifications
- Downloads
The HBP-111 occupancy sensor is designed for automatic lighting control in high or low bay applications. It contains a passive infrared (PIR) sensor and a lens engineered to provide reliable coverage from a wide range of mounting heights. Sensitivity and time delay adjustments are set using trimpots conveniently locate on the sensor and can also be adjusted remotely using a handheld configuration tool (FSIR-100). The HBP-111 includes a hold-off daylight light level feature to preventlighting from turning on wen occupancy is detected when there is sufficient ambient light available.
- Relay load ratings:
- 120VAC, 60Hz: 0-1000VA, 1/4hp
- 230VAC, 50/60Hz: 0-1000VA
- 277VAC, 60Hz: 0-1200VA, 1/4hp
- 347VAC, 60Hz: 0-1500VA, 1/4hp
- Compatible load types: Tungsten, electronic and magnetic ballasts, fluorescent and LED
- Time delay (5, 10, 15, 20, 30 min. via trimpot; 1-30 min. via FSIR-100; default 15 min.)
- Hold-off light level (1-300fc; default 300fc; disable hold-off light level via FSIR-100)
- Sensitivity (max, med, low via trimpot or FSIR-100; default max)
- Push button functions: manual mode, test mode, service mode, fail-on mode, fail-off mode, factory default, burn-in mode, walk-through mode, visual alert, service mode
- Operating conditions: Temperature 32-158"F (0-70°C); Humidity 5-95%, non-condensing
- Indoor use only
- Materials: ABS, flame retardant, impact resistant